LNG Storage Tanks

LNG
Cryogenic storage tanks for LNG are designed and manufactured for all types of bulk, satellite plant and fuel service station applications with the requirements for safe, easy and economical operation

EXPLORE LNG TANKS

LnV / LnH series tanks are vertical or horizontal, stationary pressure vessels with perlite insulation for storage of extreme cold liquid natural gas, with high quality vacuum level and low evaporation rate.

THE HIGHLIGHTS OF ISISAN TANKS ARE

  • Low operation costs and additional safety by the economizer circuit, because the boil off gas is routed into the main system via the economizer circuit taken from a top gas connection, which prevents wastage of gas.
  • In addition to our standard range of tanks, ISISAN can provide you a wide range of tailor made storage solutions up to 300,000lt with a Maximum Allowable Working Pressure of 5 bar or other pressures as required.
  • ISISAN bulk tanks are designed and manufactured in accordance with and conforming to EC directive PED 2014/68/EU and EN 13458 or other national pressure vessel codes as required.
  • ISISAN’s cryogenic tank manufacturing facility is ISO 9000 approved, to assure the best quality in all aspects of our operation.
  • The support legs used are calculated according to UBC, Eurocode standards to resist high wind and earthquake loads.
  • Carefully designed stainless steel pipe work to reduce filling operation time. Appropriate bending of stainless steel pipe work means fewer connections, minimizing potential leaks, higher operability and less servicing.
  • Operational reliability by the mono-bloc pressure building economizer-regulator for easy pressure adjustments.
  • High quality stainless steel pressure gauge and differential pressure contents gauge are standard with optional switches, transmitter and/or telemetry unit.
  • High performance safety system with dual relief valves and rupture discs by the diverter valves as standard.
  • Easily accessible valves and safety relief valve outlets directed away from the operating area, enables safe operation.
  • Rugged internal supports for safe transportation by road, container or rail.

SPECIFICATION

 Design Code EN 13458 – PED 2014/68/EU
 Max. Allowable Working Pressure 5 bar
 Design Temperature -196°C
 Inner Vessel Material Stainless Steel (According to EN 10028-7)
 Outer Vessel Material Carbon Steel (According to En 10025/EN10028-3)
 Insulation Perlite & Vacuum
Air Gas Standard Storage Tanks Dimensions

5 Bar LNG Storage Tanks

MAWPGross CapacityNet Capacity (%95 Filling)Daily Evaporation Rate (N2)0DBLWHEmpty Weight
barlitersliters% / daymmmmmmmmmmkg
5610057950.27200038204520220021902700
1000095000.25200057656300220021902700
16000152000.22275046205320295030504700
22000209000.2275061006800307030506200
32000304000.152750833090303070305010000
53000503500.13275013570142703400305014400
60000570000.1133509900106003920283017000
67000636500.10335010870117503920312019000
95000902500.10335014650153503350385025000
Data given on the table are nominal volumes and actual capacity may vary from these due to manufacturing tolerances.

P&ID

ISISAN reserves the right to change above specifications without prior notive.